What it is
A split air conditioner is "split" into two halves: the indoor section (evaporator coil + air handler/furnace blower) and the outdoor condensing unit. The condensing unit is the box in the yard with the fan on top. It holds the compressor and the condenser coil — the high-pressure, heat-rejecting side of the refrigeration cycle. "Straight-cool" means it only cools; there's no reversing valve, so it can't run backward to heat (that's a heat pump).
Everything you already know about the refrigeration cycle lives in this cabinet: the compressor raises pressure and temperature, the condenser coil rejects that heat to outdoor air, and the now-liquid refrigerant heads down the liquid line to the indoor metering device. The outdoor unit is where most electrical and high-side problems are diagnosed.
How it's built
Open the access panel and the service-port side and you'll find:
- Compressor. Usually a scroll (sometimes a reciprocating on older/smaller units). It's the pump. Single-phase residential compressors are run by a capacitor and switched by a contactor.
- Condenser coil. The fin-and-tube (or microchannel) coil wrapping the cabinet. Hot discharge gas enters, rejects heat to the air the fan pulls through it, and leaves as a subcooled liquid.
- Condenser fan motor. Pulls (or pushes) outdoor air across the coil. Driven by a run capacitor on most residential units.
- Contactor. The relay that switches line voltage (one or both legs) to the compressor and condenser fan when the indoor control calls Y.
- Run capacitor(s). A dual-round cap typically serves both the compressor (HERM terminal) and the fan (FAN terminal), with C as common. It provides the phase shift these single-phase motors need to run.
- Service valves. The liquid-line and suction-line service valves (often the suction is a ball or Schrader-equipped service valve) where you connect gauges and isolate the unit. The liquid line is the small one; suction is the big insulated one.
- Disconnect / whip. The pull-out or breakered disconnect on the wall beside the unit and the whip feeding the cabinet.
- Optional extras: a hard-start kit, a crankcase heater, a low-ambient control, high/low pressure switches, a filter-drier (sometimes outdoor).
How it's wired and plumbed
Power: 240V single-phase comes through the disconnect to the contactor. The contactor's load side feeds the compressor and the fan; the capacitor sits across the start windings to provide phase shift. Control: a 24V signal on the Y wire (from the indoor board/thermostat) energizes the contactor coil — close the contactor, the compressor and fan start. Plumbing: two copper lines tie the outdoor unit to the indoor coil — the small liquid line (warm, uninsulated) and the large suction line (cold, insulated). The metering device is at the indoor coil, so the outdoor unit sends high-pressure liquid out the liquid line and receives low-pressure vapor back on the suction line.
In the field — sequence of operation
On a cooling call: thermostat closes Y → indoor board energizes the indoor blower (G) and passes 24V out to the outdoor contactor coil → contactor pulls in → compressor and condenser fan start together → high-side pressure and temperature climb, the condenser rejects heat, refrigerant subcools and flows to the indoor metering device → the indoor coil absorbs heat from the house → vapor returns on the suction line → runs until the thermostat is satisfied, then the contactor drops out and both motors stop.
Normal values & targets
- Subcooling (TXV systems): commonly ~8–12°F at the liquid line, but charge to the manufacturer's target on the plate.
- Superheat (fixed-orifice systems): target depends on indoor wet-bulb and outdoor dry-bulb — use the charging chart/calculator, not a fixed number.
- Condenser split (condensing temp minus ambient): roughly 15–25°F on a healthy R-410A unit at design conditions; a wide split points at a dirty coil, low airflow, overcharge, or non-condensables.
- Capacitor: must read within ±6% (some say ±10%) of its stamped µF. A weak run cap drags down compressor and fan performance.
- Compressor amp draw: within RLA on the data plate; locked-rotor (LRA) means it's trying to start and not turning.
- Voltage: ~240V (or 208 commercial); large drop under load points at supply/connection problems.
Common faults & what they mean
- Unit hums but won't start / trips. Failed run capacitor, a compressor needing a hard-start, a seized compressor (LRA), or a welded/burned contactor. Check the cap first — it's the cheapest and most common.
- Fan runs, compressor doesn't (or vice versa). A dual cap with one half failed — the HERM section feeds the compressor, the FAN section feeds the fan. One dead section drops one motor.
- Contactor chatters or won't pull in. Weak 24V signal, bad coil, or low-voltage problem upstream. Contactor points pitted/welded = replace.
- High head pressure, high condenser split. Dirty condenser coil, failed/slow condenser fan, recirculating hot air, overcharge, or non-condensables. Clean and verify airflow before touching the charge.
- Low head, low suction, poor cooling. Undercharge/leak, restriction, or low indoor airflow. Confirm with superheat/subcool, not a guess.
- Compressor grounded/open/shorted. Megger and ohm the windings C-S-R. A grounded compressor often trips the breaker; an open winding won't start at all.
Tech tips & gotchas
- Check the capacitor before condemning a compressor. A huge share of "dead compressor" calls are a $20 cap. Read it under load context — a cap that's drifted low makes a good compressor look bad.
- Clean the condenser coil before you judge the charge. A plugged outdoor coil throws head pressure, subcooling, and split all off. Charging to bad readings on a dirty coil overcharges the system.
- The liquid line is the small one; suction is the big insulated one. Connect gauges to the right ports — low side on suction, high side on liquid.
- Don't add charge to fix low suction without diagnosing. Low suction can be undercharge OR low indoor airflow OR a restriction. Topping off a restricted/airflow-starved system just hides the real fault and risks flooding the compressor.
- Feel the discharge line and listen. A scroll that's pumping sounds and feels different from one slugging or running backward (a miswired three-phase scroll or a momentarily reverse-rotating one). Hot, even discharge = pumping.
Safety / code notes
- A disconnecting means within sight of the condensing unit is required per NEC §440; verify it's present and lock out before opening the cabinet. Capacitors hold a charge — discharge them before handling.
- Recover refrigerant, never vent — EPA Section 608 prohibits venting and requires certified handling and recovery.
- MCA/MOCP on the data plate govern the whip and overcurrent protection sizing.
- Refrigerant under pressure and brazing: relieve pressure properly, purge with nitrogen when brazing, and wear eye protection — liquid refrigerant causes frostbite and flash burns.